9.2
Trip Points
Adjust the Pull-In, Drop-Out, and High-Limit values for Measured-Values with the following
considerations:
–
Pull-In and Drop-Out values for the AC-Amplitude will only be available for editing,
if the user have enabled the AC-Amplitude in Configuration-Mode.
See
for more information.
–
High-Limit trip values for the Measured-Values will only be available for editing, if
the user have enabled the High-Limit function in the Configuration-Mode.
See
for more information.
–
If the Pull-In value is changed, the Drop-Out value will automatically change to the
same value as the Pull-In. To set a different Drop-Out value, make a manual change.
Intensity trip can be disabled and removed from the Flame-Logic only, if the
Flicker-Frequency sensitivity is set to a value of 65 or greater before the intensity trip
can be set to 0% (actually, in this condition the intensity trip can be set to any value
between 4 and 0).
9.3
Quality Normalization
The normalization values allow the user to increase or decrease the sensitivity of the
quality calculation.
–
A low normalization value causes less sensitivity. This causes the quality value to
rapidly change from 100% to 0%.
This rapid change may provide very little warning of a problem before the flame
proven condition is lost.
–
A high normalization value causes increased sensitivity. This causes the quality
value to change by small increments.
Operators are able to detect small changes in the flame signal. They are more likely
to spot combustion problems before they lead to a Flame-Off condition.
–
The normalization value for AC-Amplitude will only be available for editing, if the
AC-Amplitude is enabled in Configuration-Mode.
See
for more information.
–
Since the quality value is a calculated parameter and does not impact flame detection,
adjustments to the quality normalization values are not required for basic flame
detection.
8VZZ005286 B
74
9 Program-Mode
9.2 Trip Points
Содержание Uvisor SF910i
Страница 1: ...Combustion Instrumentation User Manual Uvisor SF910i Integrated SafeFlame Scanner PROCESS AUTOMATION...
Страница 2: ......
Страница 6: ......
Страница 20: ...8VZZ005286 B 20...
Страница 30: ...8VZZ005286 B 30...
Страница 67: ...Figure 7 5 Version Display in Normal Mode 8VZZ005286 B 67 7 Operating Display 7 5 Version Display...
Страница 68: ...8VZZ005286 B 68...
Страница 78: ...8VZZ005286 B 78...
Страница 90: ...8VZZ005286 B 90...
Страница 92: ...8VZZ005286 B 92...
Страница 97: ...Figure 14 2 Flame Temperature Parameters Screen 8VZZ005286 B 97 14 Flame Temperature Measurement...
Страница 98: ...8VZZ005286 B 98...
Страница 108: ...8VZZ005286 B 108...
Страница 114: ...8VZZ005286 B 114...
Страница 118: ...8VZZ005286 B 118...
Страница 125: ...8 Fit in place the SF910i Flame Scanner 8VZZ005286 B 125 19 Repair and Replacement 19 2 Fiber Optic Replacement...
Страница 126: ...8VZZ005286 B 126...
Страница 128: ...8VZZ005286 B 128...
Страница 130: ...8VZZ005286 B 130...
Страница 150: ...8VZZ005286 B 150...
Страница 151: ...Appendix E Drawings 8VZZ005286 B 151 E Drawings...
Страница 152: ...Figure E 1 Enclosure Quick Release Connector and Version LOS 8VZZ005286 B 152 E Drawings...
Страница 153: ...Figure E 2 Enclosure NPT Cable Inlet and Version LOS 8VZZ005286 B 153 E Drawings...
Страница 154: ...Figure E 3 Enclosure Quick Release Connector and Version FOC 8VZZ005286 B 154 E Drawings...
Страница 155: ...Figure E 4 Enclosure NPT Cable Inlet and Version FOC 8VZZ005286 B 155 E Drawings...
Страница 156: ...Figure E 5 FOC Flexible Assembly 8VZZ005286 B 156 E Drawings...
Страница 157: ...Figure E 6 FOC Rigid Assembly 8VZZ005286 B 157 E Drawings...
Страница 160: ...Figure E 9 Bailey Flame ON Standard Replacement 8VZZ005286 B 160 E Drawings...
Страница 161: ...Figure E 10 Typical Bailey Flame ON Installation 8VZZ005286 B 161 E Drawings...
Страница 162: ...8VZZ005286 B 162...
Страница 164: ...F 1 Earth Connection Cable Figure F 1 Earth Connections 8VZZ005286 B 164 F Cables F 1 Earth Connection Cable...
Страница 170: ...8VZZ005286 B 170...
Страница 172: ...Figure G 1 Diaphragm for SF910i FOC Scanner 8VZZ005286 B 172 G Fittings G 1 TU_KIT03 Set of Diaphragms for SF910i FOC...
Страница 178: ...G 7 Counter Flange 8VZZ005286 B 178 G Fittings G 7 Counter Flange...
Страница 179: ...Figure G 7 Boiler Mounting Counter Flange for FOC Installation 8VZZ005286 B 179 G Fittings G 7 Counter Flange...
Страница 189: ......