4. Cable connections
e) Connect the MV cables H using the H1 bolts.
NOTE
If there is more space, the circuit-breaker
compartment plate can be dismantled
f) Re-assembly of all components.
Figure 112.
Figure 113.
Cable connections
Panels
Width
Maximum
quantity of
cables per
phase
Max cross
section
of cables
(mm
2
)
LSC2A SDC
375
1
(*)
400
500
1
630
2
300
750
1
400
2
300
SFC
375
1
95
500
1
95
750
1
95
SBC/
SBC-W
750
1
630
2
300
HBC
500
1
630
2
300
DRC
375
1
(*)
400
500
1
630
2
300
UMP
750
1
400
2
300
RLC/RRC
190
1
400
LSC2B WBC/BME 600
1
630
2
400
4
300
750
2
400
4
240
(*) 2 (two) 300 mm
2
cables @ 12 Kv
Table 7. Cable connections