Primary, Nominal current and Rated secondary values are entered via parameter setting in
PCM600 (IED Configuration / Configuration / Analog inputs/Current (3I, CT))
Figure 32: Example of setting values for current sensor in PCM600
Unless otherwise specified, the
Nominal Current
setting should always be the same as the
Primary Current
setting which is a reference value for protection functions.
Each setting parameter of current protection functions is divided by application nominal cur-
rent I
n
.
Threshold for
PHIPTOC1
Start value tripping at 2 000 A is:
I
nTRIP
I
n
=
2 000 A
1 000 A
= 2
Figure 33: Example of parameter setting for PHIPTOC1 Start value in PCM600