background image

 

TZIDC, TZIDC-110, TZIDC-120

 DIGITAL POSITIONER  |  CI/TZIDC/110/120-EN REV. E 

59

 

 

 

 

Change from one to two columns 

 

 

Trademarks 

 

 

 

 

 

 

 

 

 

 

 

 

 

HART is a registered trademark of FieldComm Group, Austin, Texas, USA 

 

FOUNDATION Fieldbus is a registered trademark of FieldComm Group, Austin, 
Texas, USA. 

 

PROFIBUS and PROFIBUS PA are registered trademarks of PROFIBUS & 
PROFINET International (PI) 

 

Содержание TZIDC

Страница 1: ...onically configurable positioner with communication capabilities designed for mounting on pneumatic linear or rotary actuators Fully automatic determination of the control parameters and adaptation to...

Страница 2: ...Mounting on linear actuators 28 Mounting on rotary actuator 30 6 Electrical connections 32 Safety instructions 32 TZIDC TZIDC Control Unit terminal assignment 33 TZIDC Remote Sensor terminal assignmen...

Страница 3: ...to the product may only be performed if expressly permitted by these instructions Information and symbols on the product must be observed These may not be removed and must be fully legible at all tim...

Страница 4: ...ed to and to communicate information and data via a network interface It is operator s sole responsibility to provide and continuously ensure a secure connection between the product and your network o...

Страница 5: ...its intended use The device may only be connected when de energized The potential equalization of the system must be established in accordance with installation regulations applicable in the respecti...

Страница 6: ...ools and test devices as needed Maintenance and exchange work may be conducted by qualified specialists only i e qualified personnel in accordance with TRBS 1203 or similar Only those auxiliary compon...

Страница 7: ...ion protection specialist may modify the device The IP 65 NEMA 4x IP rating is only achieved if the splash guard is screwed in place Operating the unit without splash guard cap is prohibited The devic...

Страница 8: ...T51 C 40 to 40 C Electrical Data In intrinsically safe types of protection Ex ib IIC Ex ia IIC or Ex iaD only for connection to a certified intrinsically safe circuit Current circuit terminal Electri...

Страница 9: ...e entries that meet the requirements of EN 61241 11 for Category II 2 D as well as the ambient temperature range must be used Prevent electrostatic charging due to propagating brush discharge when the...

Страница 10: ...uited cable entries must be used that meet the requirements of EN 60079 15 IECEx Ex i and Ex n type of protection Ex marking Ex marking Marking Ex ia IIC T6 or T4 Gb Ex ib IIC T6 or T4 Gb Ex nA IIC T6...

Страница 11: ...n module for analog position feedback 31 32 U 10 to 30 V DC I 4 to 20 mA max 21 5 mA Special conditions Devices must only be connected to circuits in zone 2 if they are suitable for operation in zone...

Страница 12: ...V18345 x0x2x2xx0x Intelligent Positioner intrinsically safe with entity parameters of For use in Class I Div 1 Groups A B C and D Class II Div 1 Groups E F and G Class III Enclosure Type 4X Terminals...

Страница 13: ...nF Li 0 H Terminals Limit 2 41 42 and Limit 1 51 52 V max 15 5 V I max 52 mA Ci 20 nF Li 30 H When installed per installation Drawing No 901064 Temperature Code T4 Max Ambient temperature 85 C Note T...

Страница 14: ...ar characteristic curves and the following maximum values Current circuit terminal Electrical information maximum values Signal circuit 11 12 or Ui 24 V li 250 mA Pi 1 2 W Characteristic curve linear...

Страница 15: ...pair work was being carried out Only non flammable gases may be used for the pneumatic power supply Only suited cable entries must be used that meet the requirements of EN 60079 15 IECEx Ex i and Ex n...

Страница 16: ...me that installation or maintenance or repair work was being carried out Only non flammable gases must be used for pneumatic power supply Only suited cable entries must be used that meet the requireme...

Страница 17: ...cal variations or optional features Local communication interface LCI shall not be used in hazardous location Each pair of conductors of each intrinsic safety circuit shall be shielded See also FM ins...

Страница 18: ...n 1 Applicable Groups A B C D E F G non Incendive for Class I Division 2 Group E F and G hazardous classified indoor and outdoor NEMA 4x locations The following temperature code ratings were assigned...

Страница 19: ...tic curves and the following maximum values Current circuit terminal Electrical information maximum values Signal circuit 11 12 or Ui 24 V li 250 mA Pi 1 2 W Characteristic curve linear Li 10 H Ci 5 n...

Страница 20: ...e that installation or maintenance or repair work was being carried out Only non flammable gases may be used for the pneumatic power supply Only suited cable entries must be used that meet the require...

Страница 21: ...or maintenance or repair work was being carried out Only non flammable gases may be used for the pneumatic power supply Only suited cable entries must be used that meet the requirements of EN 60079 1...

Страница 22: ...be shielded FM approvals TZIDC 120 Positioner Model V18347 a042b2cd0e IS I II III 1 ABCDEFG T6 T5 T4 Ta 40 C 55 C 85 C 901265 Entity FISCO Entity and FISCO Parameters Terminals Type Groups Parameters...

Страница 23: ...Change from two to one column 3 Product identification Name plate 1 Full type designation 2 Software revision 3 Serial number 4 NL number 5 Year of manufacture 6 Supply air pressure 7 Input 8 Output 9...

Страница 24: ...The storage temperature should be between 40 to 85 C 40 to 185 F Avoid storing the device in permanent direct sunlight In principle the devices may be stored for an unlimited period However the warran...

Страница 25: ...ctory settings Never start automatic adjustment before restoring the factory settings Note Before assembly check whether the positioner meets the control and safety requirements for the installation l...

Страница 26: ...rical connection is performed as described in Connection on device TZIDC Control Unit with TZIDC Remote Sensor on page 40 Note To connect the TZIDC Remote Sensor a cable with the following specificati...

Страница 27: ...inear actuators The operating range for linear actuators is 45 symmetrically to the longitudinal axis The usable span within the operating range is at least 25 recommended figure 40 The usable span do...

Страница 28: ...Figure 6 Attaching a follower guide to the actuator 1 Tighten the screws so that they are hand tight 2 Attach the follower guide 1 and clamp plates 2 with screws 4 and spring washers 3 to the actuato...

Страница 29: ...uts 5 Tighten the nuts so that they are hand tight Note Adjust the height of the positioner on the cast iron yoke or columnar yoke until the lever is horizontal based on a visual check at half stroke...

Страница 30: ...lever M11031 1 2 3 5 4 1 Potentiometer lever 2 Actuator bolts 3 Valve stem 4 Valve yoke 5 Positioner Figure 11 Actuator bolts on the lever rear view M11032 1 2 3 5 4 1 Potentiometer lever 2 Actuator b...

Страница 31: ...otation direction of the actuator must be considered when determining the adapter position on axis 1 For this purpose the feedback shaft can be adjusted manually so that the adapter 3 can be attached...

Страница 32: ...ed Before opening the housing switch off the power supply The electrical connection may only be established by authorized specialist personnel Notices on electrical connection in this instruction must...

Страница 33: ...SW1 Option module 41 42 Digital feedback SW2 Option module 31 32 Analog feedback AO Option module 1 2 3 TZIDC remote sensor Only for options TZIDC Remote Sensor or TZIDC for remote position sensor Te...

Страница 34: ...optional Figure 18 TZIDC Remote Sensor Electrical Connection Change from one to two columns Connections for inputs and outputs Terminal Function comments 1 2 3 TZIDC control unit 51 52 Proximity swit...

Страница 35: ...o columns Terminal Function comments 11 12 Fieldbus bus feed 51 52 Digital feedback Limit 1 with proximity switch optional 41 42 Digital feedback Limit 2 with proximity switch optional 41 42 43 Digita...

Страница 36: ...s Terminals 11 12 11 12 Supply voltage Power feed from the Fieldbus 9 to 32 V DC 9 to 32 V DC Max permissible voltage 35 V DC 35 V DC Input Current 10 5 mA 11 5 mA Current in the event of an error 15...

Страница 37: ...0 to 100 ranges cannot overlap The module for analog feedback and the module for digital feedback have separate slots and can be used together Assembly kits for digital feedback Two proximity switches...

Страница 38: ...gital feedback 5 Terminals for basic unit Figure 20 Connection to device example Change from one to two columns 2 tap holes 14 NPT or M20 1 5 are provided on the left side of the housing for cable ent...

Страница 39: ...with wire end sleeve with plastic sleeve 0 5 to 1 5 mm2 AWG21 to AWG17 Option modules Cross section Rigid flexible wires 0 14 to 1 5 mm2 AWG26 to AWG17 Flexible with wire end sleeve no plastic sleeve...

Страница 40: ...e following options can be installed if required Optical position indicator Mechanical feedback contacts designed as proximity switches or microswitches Connect the positioner TZIDC Control Unit housi...

Страница 41: ...ensor while observing the following instructions A shielded 3 wire cable with a maximum length of 10 m 33 ft must be used for the connection Route the cable into the terminal compartment through the E...

Страница 42: ...tor To eliminate the possibility of this occurring it is recommended to install a pressure compensation valve between the springless chamber and the supply air for these types of applications It enabl...

Страница 43: ...cess failures and result in injuries Before recommissioning a positioner that was previously in use at another location always reset the device to its factory settings Never start automatic adjustment...

Страница 44: ...connections The following is now shown in the display 3 Checking mechanical mounting Press and hold down MODE and ENTER once the countdown has gone from 3 to 0 release MODE and ENTER The device switch...

Страница 45: ...to parameter 1 6 return to operating level and save the new setting Press and hold down MODE additionally quickly press 2 times The following is now shown in the display Release MODE Quickly press and...

Страница 46: ...ation standard Standard automatic adjustment Note Standard Auto Adjust does not always result in optimum control conditions Standard automatic adjustment for linear actuators 1 MODE Press and hold unt...

Страница 47: ...isplay M10906l Release MODE 4 Changing parameter settings Quickly press and release to select CTCLOCKW 5 Switching to parameter 3 3 Return to operating level and saving the new settings Press and hold...

Страница 48: ...mity switch 2 upper contact on the axis until contact is made i e just before it is inserted in the proximity switch The slot sensor enters proximity switch 2 when the feedback shaft is rotated counte...

Страница 49: ...mA is also displayed Designator display This 14 segment display with eight digits indicates the designators of the parameters with their status of the parameter groups and of the operating modes Desc...

Страница 50: ...parameterize device consult the associated operating instructions and or configuration and parameterization instructions 10Maintenance The positioner does not require any maintenance if it is used as...

Страница 51: ...tails Company Address Contact person Telephone Fax Email Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a...

Страница 52: ...52 TZIDC TZIDC 110 TZIDC 120 DIGITAL POSITIONER CI TZIDC 110 120 EN REV E 13 Appendix FM installation drawing No 901064...

Страница 53: ...TZIDC TZIDC 110 TZIDC 120 DIGITAL POSITIONER CI TZIDC 110 120 EN REV E 53...

Страница 54: ...54 TZIDC TZIDC 110 TZIDC 120 DIGITAL POSITIONER CI TZIDC 110 120 EN REV E 13 Appendix FM installation drawing No 901064...

Страница 55: ...TZIDC TZIDC 110 TZIDC 120 DIGITAL POSITIONER CI TZIDC 110 120 EN REV E 55...

Страница 56: ...56 TZIDC TZIDC 110 TZIDC 120 DIGITAL POSITIONER CI TZIDC 110 120 EN REV E 13 Appendix FM installation drawing No 901265...

Страница 57: ...TZIDC TZIDC 110 TZIDC 120 DIGITAL POSITIONER CI TZIDC 110 120 EN REV E 57...

Страница 58: ...58 TZIDC TZIDC 110 TZIDC 120 DIGITAL POSITIONER CI TZIDC 110 120 EN REV E 13 Appendix FM installation drawing No 901265...

Страница 59: ...nge from one to two columns Trademarks HART is a registered trademark of FieldComm Group Austin Texas USA FOUNDATION Fieldbus is a registered trademark of FieldComm Group Austin Texas USA PROFIBUS and...

Страница 60: ...C 110 120 EN Rev E 09 2018 We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall preva...

Отзывы: