11.15
AC input specifications
11.15.1
General AC input specifications
Parameter
Specification
Input AC power connection
3P + N + PE
Earthing systems
TN
Input voltage range
400 VAC +/- 10% (50 Hz)
Power factor at full load
>0.96
Efficiency
>94% at nominal output power
Total harmonic distortion (current)
<5%
Short circuit current rating
65 kA
11.15.2
AC input specifications (Terra Mobile 44HV)
Parameter
Specification
Maximum rated input current
62 A
Recommended input circuit breaker
63 A
Maximum power dissipation
43 kVA
11.15.3
AC input specifications (Terra Mobile 54HV)
Parameter
Specification
Maximum rated input current
78 A
Recommended input circuit breaker
80 A
Maximum power dissipation
54 kVA
11.15.4
General AC input cable specifications
Parameter
Specification
Surface and diameter
Based on current rating of the EVSE and
local regulations
Material
Copper
Maximum temperature of the input ca-
bles
75 °C (167 °F)
Minium length
n + 1 m, where n is the distance between
the power source and the EVSE
11.15.5
AC input cable specifications (Terra Mobile 44HV)
Parameter
Specification
Cross section of the phase conductors
5x16 mm²
Cross section of the PE conductor
16 mm²
Diameter of AC cable, including shielding 14.5 - 36 mm
Suggested single phase wire cross-sec-
tion
16 mm²
Technical data
9AKK108467A6997-EN | 003
59