11.5.3
Protective device compliance (Singapore)
Requirements
Specifications
Dedicated upstream safety device(s)
Emergency stop button
Dedicated upstream protection de-
vice(s)
Options:
•
RCD (Type A minimum) + MCB
•
RCBO (Type A minimum), for exam-
ple: ABB model PN: DS201 C40 A30
Upstream residual-current device (RCD) Minimum Type A, with a rated residual
operation current of maximum 30 mA
Note: Internal to EVSE is DC
fault current monitoring > 6
mA
11.6
Parts included in the delivery
Parameter
Specification
EVSE
Refer to the product label. Refer to sec-
tion
Upper mounting screws
M6 x 60
Plugs for the upper mounting screws
(servicable for a brick wall)
8 x 60 mm
Lower mounting screws
M6 x 120
Plugs for the lower mounting screws
(servicable for a brick wall)
10 x 60 mm
Installation template
-
RFID card
MIFARE
Label with PIN
To log in to the
TerraConfig app.
11.7
Required tools for installation
Parameter
Specifications
Hammer
-
Spirit level
-
Drill
-
Torque screwdriver, cross
-
Torque screwdriver, slotted
For terminal blocks and plugs with 5 mm
pitch
Technical data
66
BCM.V3Y01.0-EN | 002