Parameter
Function or specification
MV switch
Dedicated MV/LV transformer for indus-
trial use of the EVSE
For residential use of the EVSE you can
connect directly to low voltage public
grid
Automatic circuit breaker
Output 4 x 400 A, 690 Vac
Additional option: Residual current
breaker type B
Caution: A
residual
current
breaker
type B is
Mandatory
for an EVSE
with CHA-
deMO out-
put.
Output 4 x 400 A, gG Fuses, 690 Vac
Adjustable Idn 30 to 300 mA
10.21
In-rush current
Current peaks during the start of a charge session
Parameter
Specification [µs]
Duration of the current peaks
25
Maximum current peak (400 VAC and 50/60 Hz)
Parameter
Specification [A]
Terra 360
< 458 duration 1.68 ms
Terra 180
< 458 duration 1.68 ms
Terra 60
< 152 duration 1.5 ms
Maximum current peak (480 VAC)
Parameter
Specification [A]
Terra 360
< 550 duration 1.68 ms
Terra 180
< 550 duration 1.68 ms
Terra 60
< 183 duration 1.5 ms
10.22
Cleaning specifications
Parameter
Specification
Cleaning agent
pH value between 6 and 8
Non-abrasive tool
Non-woven nylon hand pad
Technical data
128
9AKK108467A6398-EN | 002
Содержание Terra 180 CE
Страница 1: ...Operation and installation manual Terra 360 180 60 CE Copyright ABB All rights reserved ...
Страница 92: ...Procedure 1 Remove these parts 1 Fasteners A 2 Border covers B B A Access to parts 92 9AKK108467A6398 EN 002 ...
Страница 129: ...11 Appendix 11 1 Declaration of conformity Appendix 9AKK108467A6398 EN 002 129 ...
Страница 130: ...Appendix 130 9AKK108467A6398 EN 002 ...
Страница 134: ......