43/78 SUREWAVE SFC USER MANUAL
P287-C-2
Stop
(Controlled)
Stops the system when running, when droop enabled, the
system is first unloaded, when standalone the system will
ramp down the output voltage prior to stopping.
P287-C-3
Reset
Rising edge will cause application & PEBB reset.
Faults will not necessarily be cleared.
P287-C-4
Droop enable
When this input goes high (closes), system will transfer
from isochronous to V
droop
, F
droop
mode for parallel opera-
tion.
If fix power input is high, Droop enable input is overridden.
P287-C-5
Fix power
Applicable only in Virtual Generator mode.
When enabled (high), output power and VARs are sourced
based on P
set
and Q
set
.
P287-C-6
Load enable
Applicable only in Virtual Generator mode, used to bump-
lessly load or unload the SFC. When enabled (High) the load
is ramped to the SFC at a fixed rate, when disabled (Low)
the load is offloaded to the other sources.
P287-C-7
Synchronize
Used to synchronize system to another AC bus.
P287-C-8
NA
NA
Table 9-1: Summary of control inputs
9.2.2 Digital outputs
A number of digital outputs are provided, to provide status signals for the customer. Note that
these outputs are electronic, rated at 24V 1A each. For remote signaling, suitable relays will
need to be fitted and their coils wired to the respective digital outputs.
Table 9-2 summarizes these digital outputs.
Figure 9-5: User digital outputs