600T & 600T EN PRESSURE TRANSMITTER
CALIBRATION
Q - 26
Set Output %
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select
YES
.
Select
SET OUTPUT
%.
If digitally configured, the
D-TO-A ADJUST
selection
will not appear.
Select LOW and press
. (Procedure for
HIGH selection is identical).
Display indicates present data.
Enter LOW value,
.
C A LI-
B R AT E
E N T E R
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
[ 3 TIMES ]
E N T E R
CALIBRATION
SENSOR TRIM
D-TO-A ADJUST
PV BIAS
→
SET OUTPUT %
E N T E R
SET OUTPUT %
→
LOW
HIGH
ENTER
E N T E R
OP %: nnn.nn %
PV VAL:
value
units
Hit ENTER to set OP%
E N T E R
ENTER NEW VALUE
value
%
ENTER
E N T E R
ID TAGNAME
READY