TZID/AZH POSITIONER
CALIBRATION
M
-
7
Lever Zero Position
This function assigns the zero position of the lever range to one of the
stops. The lever zero position determines whether the zero position of
the valve is allocated to the lever shaft turning counterclockwise or
turning clockwise (looking into the open device cover).
Enter a minimum valve range and press
.
Enter a maximum valve range.
Select
YES
to make the changes permanent.
Manual range adjust is complete.
Key
Display
Comments
E N T E R
ENTER VALVE RANGE AS
% LEVER RANGE.
VALVE RANGE MUST NOT
BE LESS THAN 10 %
MIN VALVE RANGE
nnn.nn %
MAX VALVE RANGE
nnn.nn %
ENTER
E N T E R
MAKE CHANGES
PERMANENT ?
NO
→
YES
E N T E R
ID TAGNAME
READY
Key
Display
Comments
Select
LEVER ZERO POSITION
.
C A LI-
B R AT E
AUTOSTROKE
MANUAL RANGE ADJUST
→
LEVER ZERO POSITION
SPRING ACTION ACTUA