6.6.
Configuring by using imported CID file
If you have to configure several SPA-ZC 402 with the similar IEC 61850 data object
model, it is possible to import a previously generated CID file and change the
communication addresses, typically by changing the IP address.
1. Create the project and add the logical device LD0 like in Section 6.4. Building
2. Add a logical device to the SPA-ZC 40x Device object by right-clicking to select
SPA-ZC 40x > New > Communication > Logical Device
.
3. Select the CID import function by choosing a new empty logical node and then
right-click to select the CID import function.
In the CID import dialog you can select the right CID file from the workstation
directory and import it to a previously created logical node. LD0 contains the data
sets and reporting control blocks. Other logical devices describe the data model of a
connected IED.
6.7.
Configuring communication parameters
SPA-ZC 402 communication parameters are located in the device properties.
SPA-ZC 402 uses static IP addresses, which have to be defined in the planned
network structure.
*
IP Address
IP address identifies SPA-ZC 402 in Local Area Network (LAN). All
communication via SPA-ZC 402 uses this address. The default value is
192.168.2.10 and it has to be changed to a unique address according to the
planned network structure.
*
Default Gateway
This IP address defines the gateway's address, which forwards IP traffic between
the local subnet and outside world. The default value is 192.168.2.1 and it has to
be changed according to the planned network structure.
*
Subnet Mask
This subnet mask defines which addresses are not in the local subnet and must be
accessed through the default gateway.
*
SNTP Servers
SPA-ZC 402 uses SNTP for its own realtime clock. The time is used for
synchronizing the IED with SPA time synchronization. One SNTP Server has to
exist in the accessible network, otherwise the SPA-ZC 402 event time stamping
is not working properly. The primary server is mainly in use. The secondary
SNTP server is used, if the primary SNTP server cannot be reached. While using
the secondary SNTP server, SPA-ZC 402 tries to change to the primary server in
every third SNTP request attempt. The primary server is used, if the request is
succeeded.
38
SPA-ZC 402
SPA-ZC 402
SPA/ Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1MRS755380
Содержание SPA-ZC 402
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 28: ...28 ...
Страница 54: ...54 ...
Страница 58: ...58 ...
Страница 68: ...68 ...
Страница 104: ...104 ...
Страница 106: ...106 ...
Страница 108: ...108 ...
Страница 110: ...110 ...