Videographic Recorder
SM1000
4 Configuration
76
IM/SM1000
Issue 11
Specify the display range and units of the engineering value
corresponding to the electrical high and low values, within the
limits defined in Table 4.3:
1
THC/RTD
°C
°F
Type
Min.
Max.
Min.
Max.
Type B
–18
1800
0
3270
Type E
–100
900
–140
1650
Type J
–100
900
–140
1650
Type K
–100
1300
–140
2350
Type L
–100
900
–140
1650
Type N
–200
1300
–325
2350
Type R & S
–18
1700
0
3090
Type T
–250
300
–400
570
Pt100
–200
600
–325
1100
Power 5/2
–999 to +9999
Power 3/2
Square Root
Custom Linearizer 1
Custom Linearizer 2
Linear
Table 4.3 Limits of Engineering Ranges
Example
– for an electrical input range of 4.0 to 20.0mA,
representing a pressure range of 50 to 250 bar, set the 'Low'
value to 50.0 and the 'High' value to 250.0.
Enter the tag name to be displayed on channel indicators and
used to identify the channel in archive files (8 characters max.).
Note.
Tags with a high percentage of capital letters and wide
characters such as 'W' or 'M' may appear truncated in some
Operator Views. In such cases, use lower case letters or fewer
characters.
Enter the tag name to be displayed in the Process view and
used in the archive files (20 characters max.).
•1
If this parameter is changed, internally recorded data files are recreated and unarchived data is lost.