82
SCU200
INSITE ENERGY MANAGEMENT SYSTEM
7.1.2.Energy meter module readings
7.1.3.I/O modules readings
• I/O modules readings
Insite pro M allows to connect up to 8 I/O modules (in the case no other device is connected – maximum
device count is 32 and one I/O module counts as 8 devices). I/O modules can be assigned to Modbus ID
from 1 to 32 and can be read/control using web UI and Modbus TCP/RTU protocols.
For direct reading using Modbus protocol, IO module registers map is provided below.
Please note that addresses 0-3 (status contacts) could be read using Modbus function 01 (read coils) as
well as function 03 (read holding registers). All other registers are being read with function 03.
Cate-
gory
Quantity External
Modbus
data type
IO
module
address
External
Modbus
registers
Writable IO
module
Modbus
IO
module
web-
server
IO
module
storage
External
Modbus
IO
module
I/O
configu-
ration
Unsigned
integer
40
1
yes
0
0
0
1
IO
module
Pulse
Counter
Port 0
Unsigned
integer
50
2
no
1
1
1
1
IO
module
Pulse
Counter
Port 1
Unsigned
integer
52
2
no
1
1
1
1
IO
module
Pulse
Counter
Port 2
Unsigned
integer
54
2
no
1
1
1
1
IO
module
Pulse
Counter
Port 3
Unsigned
integer
56
2
no
1
1
1
1
IO
module
Status
Contacts
Port 0
Unsigned
integer
0
1
yes
1
1
1
1
IO
module
Status
Contacts
Port 1
Unsigned
integer
1
1
yes
1
1
1
1
IO
module
Status
Contacts
Port 2
Unsigned
integer
2
1
yes
1
1
1
1
IO
module
Status
Contacts
Port 3
Unsigned
integer
3
1
yes
1
1
1
1
7.1.4.ABB meters readings
SCU200 allows connecting up to 16 RTU devices including meters with RS-485 interface. Supported meter
types are ABB M4M/M1M, M2M, DMTME, IM300, EV meters and EQ meters. Each meter can be assigned to
Modbus ID from 33 to 48 and is available under My plant->Devices->Modbus RTU devices.
After adding RTU device with specific type, the device is scanned for responding registers. In case if 3rd
party RTU device is added outside of known device models, user should upload own device descriptor
which will be used by SCU200 for creating device registers map.
RTU devices don’t have to have uniform Modbus configuration. SCU200 will adapt readout coniguration in
case if different devices have different baudrates, parities etc. If a device stops responding (disconnects,
encounters fault or because of any other reason), it will be excluded from readout queue for an hour. After
an hour another readout attempt will be made and once responds correctly, it will be read as usual.
Содержание SCU200
Страница 1: ...SCU200 User manual 1 0 1 INSITE ENERGY MANAGEMENT SYSTEM SCU200 User manual ...
Страница 2: ......
Страница 77: ...77 SCU200 INSITE ENERGY MANAGEMENT SYSTEM ...