1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 121
Additional functions
34 - Power Controller
Description
The
Power Controller
function allows managing the loads of a system according to the power
absorbed to reduce consumption and optimize energy efficiency.
All the parameters and measurements of the function are available via Ekip Connect, while the
Trip unit allows setting and viewing some of them, as noted below.
IMPORTANT: for full details see the Technical Catalog (see page 4) or the
function's White Paper (see page 12).
Ekip Touch
Parameters
Some function configuration parameters are available In the
Settings - Power Controller
menu
Parameter
Description
Default
Enable
Enable/disable the function and the availability of the parameters in
the menu
OFF
Load
Operating
Mode
Allows setting the configuration of each of the 15 programmable
loads (from Load 1 to Load 15). It is possible to choose between
Automatic or Manual configuration
Manual
Powers
Limits
Allows setting the 10 power limits (from Power Limit 1 to Power
Limit 10). The value is expressed in kW and can be set in a range
of: 10 kW .. 10000 kW with 10 kW steps.
10 kW
NOTE: to set all the parameters of the function it is recommended to first configure the
parameters via Ekip Connect, and only then work on the Trip unit to enable or change
loads and power limits
Ekip Touch
Measurements
In the
summary pages
, with Power Controller activated the specific page with the main
measurements is available:
Measurement
Description
Ea
Expected energy
T
Time spent within the evaluation window
LOADS
Number of controlled loads
LOADS Shed
Number of loads shed
With
Power Controller
activated, the
Power Controller
menu is available in the
Information
page
(page 30), and it provides information on the 15 loads in 2 submenus:
Submenu
Information included
Load Input Status
Load status (from Load 1 to Load 15): open or closed
Active load
Load configuration (from Load 1 to Load 15): active or inactive
Содержание SACE Tmax XT2
Страница 82: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 82 L curve IEC 60255 151 SI L curve IEC 60255 151 VI ...
Страница 83: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 83 L curve IEC 60255 151 EI L curve t k I4 ...
Страница 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Страница 85: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 85 S curve t k Curve S2 I curve MCR curve 2I curve ...
Страница 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Страница 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Страница 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Страница 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Страница 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Страница 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Страница 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Страница 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Страница 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Страница 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...
Страница 207: ...1SDH002031A1002 ECN000092998 Rev B ...