30 - Network Analyzer
Presentation
The Network Analyzer function allows setting voltage and current checks for a long time, to
analyze the system's operation.
For this purpose, voltages and currents are monitored to detect:
Voltage sequences (Over, Under, Pos and neg)
Voltage imbalance (Unbalanced)
Voltage drops, of a short duration (Interruptions) and slow (Sag)
Voltage increases, of a short duration (Spike) and slow (Swell)
Harmonic distortion of voltages and currents (THD)
Each monitor is associated with control parameters that can be set by the user and to counters
that are incremented each time the control condition settings are reached.
Parameters
The counter configuration parameters are available in the
Settings - Network Analyzer
menu
In the
Settings
menu it is also possible to set the
Measurement interval
parameter, which defines
the period of each control session.
NOTE: the parameter is the same used for current measurements and maximum
voltages
Main Menu
Parameter
Description
Default
Enable
Enable/disable the function and the availability of the parameters in
the menu
OFF
I Harmonic Analysis
Activates the harmonic analysis of the currents
OFF
V Harmonic Analysis
Activates the harmonic analysis of the voltages
OFF
V Low Threshold
Counter control threshold
Under V Th
The value is expressed as a percentage of the rated voltage Un,
which can be set in a range of: 75% .. 95% Un, with 5% steps
85 % Un
V High Threshold
Counter control threshold
Over V Th
The value is expressed as a percentage of the rated voltage Un,
which can be set in a range between: 105, 110, 115% Un
110 % Un
Imbalance V Th
Counter control threshold
Unbalanced
.
The value is expressed as a percentage of the rated voltage Un,
which can be set in a range of: 2% .. 10% Un, with 1% steps
NOTE: 0% = symmetrical and balanced system
3 % Un
V Interruption Th
Counter control threshold
V interruption
.
The value is expressed as a percentage of the rated voltage Un,
which can be set in a range of: 10% .. 95% Un, with 5% steps
95 % Un
V Spike Threshold
Counter control threshold
Spikes
.
The value is expressed as a percentage of Un, which can be set in
a range of: 105% .. 125% Un, with 5% steps
105 % Un
Sags
Menu with the control parameters for voltage sags
Surges
Menu with the control parameters for voltage surges
Harmonics
Available by enabling the harmonic analysis of currents and/or
voltages, the menu allows configuring the harmonic control
parameters
Содержание SACE Tmax XT2
Страница 82: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 82 L curve IEC 60255 151 SI L curve IEC 60255 151 VI ...
Страница 83: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 83 L curve IEC 60255 151 EI L curve t k I4 ...
Страница 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Страница 85: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 85 S curve t k Curve S2 I curve MCR curve 2I curve ...
Страница 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Страница 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Страница 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Страница 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Страница 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Страница 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Страница 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Страница 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Страница 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Страница 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...
Страница 207: ...1SDH002031A1002 ECN000092998 Rev B ...