ABB | SACE Emax 2
Electronic accessories | 10 - Ekip Com Modbus TCP modules
223 | © 2017 ABB | 1SDH001330R0002 - ECN000058721 Rev. A
Continued from the previous page
The following table shows the path from the display for accessing information on the modules:
About
Protection Unit
Circuit-breaker
Modules
…
Ekip Com Modbus TCP
Ekip Com Modbus TCP *R
…
Power Controller
Information that can be displayed on the modules:
• The serial number and the software version.
• The IP address, the Network Mask, and the Gateway Address.
• TCP Clients.
• The MAC Address.
The following table shows the information on the modules:
Information
Description
IP Address
This is the address assigned to the modules at the moment of connection to the
network. It consists of four bytes (for a total of 32 bits), each of which can have a
value from 0 to 255.
By default, allocation is dynamic. With dynamic allocation, the modules wait to receive
the IP address from a DHCP server.
Without a DHCP server, the modules adopt an Autoconfiguration IP Address in the
range 169.254.xxx.xxx, calculated in a pseudo random manner so as to be the same
at every switch-on.
As an alternative, you can enable the static IP address option, which allows the IP
address to be forced. In this case, you must make sure that the IP Address inserted is
different from that of the other devices connected to the same network.
Network Mask
This is the subnet mask, and identifies the method to recognize the subnet to which
the modules belong, with the possibility of searching for the modules within a defined
set of recipients.
If you enable the option Static IP Address, you must also enter the correct Network
Mask.
Gateway Address
It is the IP address of the node to which the modules are connected, in case of
multiple subnets.
If you enable the Static IP Address option, you must also enter the correct Gateway
Address.
TCP Client
There are three IP Addresses of the client devices connected to the modules.
MAC Address
It is the address assigned by ABB, having an OUI equal to ac:d3:64
(1)
.
(1)
Organizationally Unique Identifier, formed by the first three bytes of a MAC address, and which uniquely
identifies the manufacturer of an Ethernet device.
Содержание SACE Emax E1.2
Страница 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Страница 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...
Страница 311: ...1SDH001330R0002 ECN000058721 Rev A ...