Ekip Touch protection trip unit | 18 - Test
18 - Test
Path
Main page - Menu - Test
Presentation
All the trip units of the Ekip Touch range allow you to carry out various checks directly from the display:
•
Autotest
, for the check on the display and the LEDs.
•
Trip Test
, for the check on the circuit breaker opening command.
•
Test CB
, for the check on the controls of the circuit-breaker opening and closing coils
•
Zone Selectivity
, for the check on Zone Selectivity inputs and outputs.
In the presence of auxiliary power supply and contact type modules, the dedicated sections are enabled:
•
Ekip Signalling 4K
allows the check of LED and contacts of the module.
•
Ekip Signalling 2K-1, 2K-2, 2K-3
allows the check of LED and contacts of the module.
•
Ekip Signalling 10K-1, 10K-2, 10K-3
allows LEDs to be checked and contact closing commands to
be sent.
In the presence of an Rc type trip unit and auxiliary power supply, the dedicated test section is enabled:
•
Rc Test
allows you to check connection and proper operation of the toroid Rc
NOTE:
access to the Test Menu requires the insertion of the password.
Using the Ekip T&P and Ekip Bluetooth test accessories it is also possible to check the operation of the
electronic protections from a PC, by simulating various installation conditions.
Autotest
The automatic sequence of the display and the LED is activated by selecting the command
Autotest.
The sequence includes the following test phases:
Phase
Operation
1
Screen with message “www.abb.com”
2
Darkening of the display
3
Color sequence with red, green, blue bands, with gradual increase of backlighting
4
Warning and Alarm LEDs switched on for 1 second
Trip Test
Selecting the command
Trip test
opens a dedicated page that asks you to confirm running the test by
pressing the iTest key for at least 7 seconds.
When the key is pressed, an opening command is sent to the trip coil.
IMPORTANT: the opening command is performed with circuit-breaker closed and
absence of circulating currents.
Test CB
Selecting the command
Test CB
opens a submenu containing the commands
Open CB
and
Close CB.
The commands allow you to activate coil opening and closing respectively: the correct sending of the
command is confirmed by a window with the message “Test Executed”.
The correct operation of the entire command system (trip unit, Ekip Com Actuator and opening and closing
coils) is verified through the opening and/or the closing of the circuit-breaker.
Continued on the next page
Содержание SACE Emax E1.2
Страница 2: ...ABB SACE Emax 2 2 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 8: ...VI 2017 ABB SACE Emax 2 1SDH001330R0002 ECN000058721 Rev A ...
Страница 9: ...ABB SACE Emax 2 3 2017 ABB 1SDH001330R0002 ECN000058721 Rev A ...
Страница 310: ...ABB SACE Emax 2 304 2017 ABB 1SDH001330R0002 ECN000058721 Rev A Service 1 Power Care ...
Страница 311: ...1SDH001330R0002 ECN000058721 Rev A ...