19.7
Data communication interfaces
Table 544:
Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
100BASE-TX
-
CAT 6 S/FTP or better
100 MBits/s
100BASE-FX
TCP/IP protocol
Fibre-optic cable with
LC connector
100 MBits/s
Table 545:
Fibre-optic communication link
Wave length
Fibre type
Connector
Permitted path
attenuation
1)
Distance
1300 nm
MM 62.5/125
μm glass fibre
core
LC
<8 dB
2 km
1) Maximum allowed attenuation caused by connectors and cable together
Table 546:
X8/IRIG-B and EIA-485 interface
Type
Protocol
Cable
Tension clamp
connection
IRIG-B
Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841-
9844) or Alpha Wire (Alpha 6222-6230)
Tension clamp
connection
IEC 68070–5–103
DNP3.0
Shielded twisted pair cable
Recommended: DESCAFLEX RD-
H(ST)H-2x2x0.22mm
2
, Belden 9729, Belden
9829
Table 547:
IRIG-B
Type
Value
Accuracy
Input impedance
430 Ohm
-
Minimum input voltage
HIGH
4.3 V
-
Maximum input voltage
LOW
0.8 V
-
Table 548:
EIA-485 interface
Type
Value
Conditions
Minimum differential
driver output voltage
1.5 V
–
Maximum output
current
60 mA
-
Minimum differential
receiver input voltage
0.2 V
-
Table continues on next page
Section 19
1MRK 504 135-UEN A
Technical data
618
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...