Even if the
AnalogInputType
setting of a SMAI block is set to
Current
, the
MinValFreqMeas
setting is still visible. This means that
the minimum level for current amplitude is based on
UBase
. For
example, if
UBase
is 20000, the minimum amplitude for current is
20000 * 10% = 2000. This has practical affect only if the current
measuring SMAI is used as a frequency reference for the adaptive
DFT. This is not recommended, see the Setting guidelines.
17.9.6
Operation principle
Every SMAI can receive four analog signals (three phases and one neutral value),
either voltage or current. The
AnalogInputType
setting should be set according to the
input connected. The signal received by SMAI is processed internally and in total 244
different electrical parameters are obtained for example RMS value, peak-to-peak,
frequency and so on. The activation of
BLOCK
input resets all outputs to 0.
SMAI_20 does all the calculation based on nominal 20 samples per line frequency
period, this gives a sample frequency of 1 kHz at 50 Hz nominal line frequency and 1.2
kHz at 60 Hz nominal line frequency.
The output signals
AI1
...
AI4
in SMAI_20_x function block are direct outputs of the
connected input signals
GRPxL1
,
GRPxL2
,
GRPxL3
and
GRPxN
.
GRPxN
is always
the neutral current. If
GRPxN
is not connected, the output
AI4
is zero. The
AIN
output
is the calculated residual quantity, obtained as a sum of inputs
GRPxL1
,
GRPxL2
and
GRPxL3
but is equal to output
AI4
if
GRPxN
is connected. The outputs signal
AI1
,
AI2
,
AI3
and
AIN
are normally connected to the analog disturbance recorder.
The SMAI function block always calculates the residual quantities in
case only the three phases (Ph-N) are connected (
GRPxN
input not
used).
The output signal
AI3P
in the SMAI function block is a group output signal
containing all processed electrical information from inputs
GRPxL1
,
GRPxL2
,
GRPxL3
and
GRPxN
. Applications with a few exceptions shall always be connected
to
AI3P
.
The input signal
REVROT
is used to reverse the phase order.
A few points need to be ensured for SMAI to process the analog signal correctly.
1MRK 504 135-UEN A
Section 17
Basic IED functions
585
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...