16.9.2
Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
16.9.3
Function block
IEC10000251-1-en.vsd
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V1 EN
Figure 244:
GOOSEMVRCV function block
16.9.4
Signals
Table 460:
GOOSEMVRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 461:
GOOSEMVRCV Output signals
Name
Type
Description
MVOUT
REAL
Measurand value output
DATAVALID
BOOLEAN
Data valid for measurand value output
COMMVALID
BOOLEAN
Communication valid for measurand value output
TEST
BOOLEAN
Test output
16.9.5
Settings
Table 462:
GOOSEMVRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
16.9.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
1MRK 504 135-UEN A
Section 16
Station communication
547
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...