14.5.2
Function block
The Indications function has no function block of it’s own.
14.5.3
Signals
14.5.3.1
Input signals
The Indications function logs the same binary input signals as the Disturbance report
function.
14.5.4
Operation principle
The LED indications display this information:
Green LED:
Steady light
In Service
Flashing light
Internal fail
Dark
No power supply
Yellow LED:
Function controlled by
SetLEDn
setting in Disturbance report function.
Red LED:
Function controlled by
SetLEDn
setting in Disturbance report function.
Indication list:
The possible indication signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
•
the signal must be connected to binary input BxRBDR function block
•
the DRPRDRE parameter
Operation
must be set
On
•
the DRPRDRE must be trigged (binary or analog)
•
the input signal must change state from logical 0 to 1 during the recording time.
Indications are selected with the indication mask (
IndicationMask
) when setting the
binary inputs.
Section 14
1MRK 504 135-UEN A
Monitoring
474
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...