AND
BLOCK
TRIN
Operation Mode = On
OR
t
tTripMin
TRIP
en05000789.vsd
Program = 3Ph
IEC05000789 V1 EN
Figure 164:
Simplified logic diagram for three phase trip
Lockout can be activated either by activating the input (SETLKOUT) or
automatically from trip input by setting
AutoLock
to
On
. A Lockout condition will be
indicated by activation of the output (CLLKOUT). If lockout has been activated it can
be reset by activating the input (RSTLKOUT) or via the HMI.
If
TripLockout
is set to
On
an active Lockout will result in a three-phase trip output.
In this way if both
AutoLock
and
TripLockout
are set to
On
the trip will always be
three-phase and sealed in.
13.1.7
Technical data
Table 278:
SMPPTRC technical data
Function
Range or value
Accuracy
Trip action
3-ph
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
13.2
Trip matrix logic TMAGGIO
13.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic
TMAGGIO
-
-
13.2.2
Functionality
The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route
trip signals and other logical output signals to the tripping logics SMPPTRC and
SPTPTRC or to different output contacts on the IED.
1MRK 504 135-UEN A
Section 13
Logic
373
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...