12.6.5
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
12.6.6
Operation principle
Upon receiving the input signals, the IEC 61850 generic communication I/O functions
(DPGGIO) function block will send the signals over IEC 61850-8-1 to the equipment
or system that requests these signals. To be able to get the signals, PCM600 must be
used to define which function block in which equipment or system should receive this
information.
12.7
Single point generic control 8 signals SPC8GGIO
12.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals
SPC8GGIO
-
-
12.7.2
Functionality
The Single point generic control 8 signals SPC8GGIO function block is a collection
of 8 single point commands, designed to bring in commands from REMOTE
(SCADA) to those parts of the logic configuration that do not need extensive
command receiving functionality (for example, SCSWI). In this way, simple
commands can be sent directly to the IED outputs, without confirmation. The
commands can be pulsed or steady with a settable pulse time.
12.7.3
Function block
SPC8GGIO
BLOCK
PSTO
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
IEC09000086_1_en.vsd
IEC09000086 V1 EN
Figure 156:
SPC8GGIO function block
1MRK 504 135-UEN A
Section 12
Control
359
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...