10.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Overfrequency protection
SAPTOF
f >
SYMBOL-O V1 EN
81
10.2.2
Functionality
Overfrequency protection function SAPTOF is applicable in all situations, where
reliable detection of high fundamental power system frequency is needed.
Overfrequency occurs because of sudden load drops or shunt faults in the power
network. Close to the generating plant, generator governor problems can also cause
over frequency.
SAPTOF measures frequency with high accuracy, and is used mainly for generation
shedding and remedial action schemes. It is also used as a frequency stage initiating
load restoring. A definite time delay is provided for operate.
SAPTOF is provided with an undervoltage blocking.
10.2.3
Function block
SAPTOF
U3P*
BLOCK
TRIP
START
BLKDMAGN
IEC09000280_1_en.vsd
IEC09000280 V1 EN
Figure 105:
SAPTOF function block
10.2.4
Signals
Table 159:
SAPTOF Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
1MRK 504 135-UEN A
Section 10
Frequency protection
235
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...