adjacent parts in a relatively short time. The function has settable inverse operating
curves and independent alarm stages.
9.4.3
Function block
OEXPVPH
U3P*
BLOCK
RESET
TRIP
START
ALARM
IEC09000008-2-en.vsd
IEC09000008 V2 EN
Figure 98:
OEXPVPH function block
9.4.4
Signals
Table 148:
OEXPVPH Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltages
BLOCK
BOOLEAN
0
Block of function
RESET
BOOLEAN
0
Reset of function
Table 149:
OEXPVPH Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
START
BOOLEAN
General start signal
ALARM
BOOLEAN
Overexcitation alarm signal
9.4.5
Settings
Table 150:
OEXPVPH Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
V/Hz>
100.0 - 180.0
%UB/f
0.1
110.0
Operate level of V/Hz at no load and rated
freq in % of (Ubase/frated)
V/Hz>>
100.0 - 200.0
%UB/f
0.1
140.0
High level of V/Hz above which tMin is
used, in % of (Ubase/frated)
tMin
0.005 - 60.000
s
0.001
7.000
Minimum trip delay for V/Hz curve
kForIEEE
1 - 60
-
1
1
Time multiplier for IEEE inverse type
curve
AlarmLevel
50.0 - 120.0
%
0.1
100.0
Alarm operate level
tAlarm
0.00 - 9000.00
s
0.01
5.00
Alarm time delay
Section 9
1MRK 504 135-UEN A
Voltage protection
222
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...