Table 10:
CT input channels used for the LV side CTs
Setting parameter
Selected value for both solutions
CTprim
800
CTsec
5
CTStarPoint
ToObject
5. Enter the following settings for all three CT input channels used for the HV side
CTs, see table
.
Table 11:
CT input channels used for the HV side CTs
Setting parameter
Selected value for solution 1 (star
connected CT)
Selected value for solution 2
(delta connected CT)
CTprim
300
300
173
3
=
EQUATION1888 V1 EN-US
(Equation 12)
CTsec
5
5
CTStarPoint
From Object
ToObject
To compensate for delta connected CTs, see equation
.
6. Enter the following values for the general settings of the Transformer differential
protection function, see table
.
Table 12:
General settings of the differential protection function
Setting parameter
Select value for solution 1 (star
connected CT)
Selected value for solution 2
(delta connected CT)
GlobalBaseSelW1
CTPrim / GlobalBaseSelW1
(CTPrim /
GlobalBaseSelW1) / sqrt(3)
GlobalBaseSelW2
CTPrim / GlobalBaseSelW2
(CTPrim /
GlobalBaseSelW2) / sqrt(3)
GlobalBaseSelW3
CTPrim / GlobalBaseSelW3
(CTPrim /
GlobalBaseSelW3) / sqrt(3)
ConnectTypeW1
STAR (Y)
STAR (Y)
ConnectTypeW2
delta=d
star=y
1)
ClockNumberW2
1 [30 deg lag]
0 [0 deg]
1)
ZSCurrSubtrW1
On
Off
2)
ZSCurrSubtrW2
Off
Off
TconfigForW1
No
No
TconfigForW2
No
No
Table continues on next page
Section 6
1MRK 504 169-UEN A
Differential protection
88
Transformer protection RET650 2.2 IEC
Application manual
Содержание ret650
Страница 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Страница 2: ......
Страница 28: ...22...
Страница 38: ...32...
Страница 42: ...36...
Страница 80: ...74...
Страница 168: ...162...
Страница 174: ...168...
Страница 250: ...244...
Страница 346: ...340...
Страница 366: ...360...
Страница 390: ...384...
Страница 391: ...385...