100
2
2
3
IBase
I
I
EQUATION1520 V5 EN-US
(Equation 41)
where:
I2
is the maximal negative sequence current during normal operating conditions, plus a margin
of 10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
10.2.3.4
Zero sequence based
M13683-43 v8
The IED setting value
3U0>
is given in percentage of the base voltage
UBase
. The
setting of
3U0>
should not be set lower than the value that is calculated according
100
3
0
3
0
3
UBase
U
U
EQUATION1521 V4 EN-US
(Equation 42)
where:
3U0
is the maximal zero sequence voltage during normal operation conditions, plus a margin of
10...20%
UBase is the base voltage for the function according to the setting
GlobalBaseSel
The setting of the current limit
3I0<
is done in percentage of
IBase
. The setting of
3I0<
must be higher than the normal unbalance current that might exist in the
system. The setting can be calculated according to equation
3 0
3 0
100
I
I
IBase
=
×
<
EQUATION2293 V3 EN-US
(Equation 43)
where:
3I0<
is the maximal zero sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting
GlobalBaseSel
10.2.3.5
Delta U and delta I
GUID-02336F26-98C0-419D-8759-45F5F12580DE v7
Set the operation mode selector
OpDUDI
to
On
if the delta function shall be in
operation.
1MRK 504 169-UEN A
Section 10
Secondary system supervision
Transformer protection RET650 2.2 IEC
173
Application manual
Содержание ret650
Страница 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Страница 2: ......
Страница 28: ...22...
Страница 38: ...32...
Страница 42: ...36...
Страница 80: ...74...
Страница 168: ...162...
Страница 174: ...168...
Страница 250: ...244...
Страница 346: ...340...
Страница 366: ...360...
Страница 390: ...384...
Страница 391: ...385...