) 100
s
IN
I
IBase
IECEQUATION17003 V1 EN-US
(Equation 30)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (
IBase
).
Operation
: set the protection to
On
or
Off
.
IN>>
: Set operate current in % of
IB
.
IN>>Max
and
IN>>Min
should only be changed if remote setting of operation
current level,
IN>>
, is used. The limits are used for decreasing the used range of
the
IN>>
setting. If
IN>>
is set outside
IN>>Max
and
IN>>Min
, the closest of the
limits to
IN>>
is used by the function. If
IN>>Max
is smaller than
IN>>Min
, the
limits are swapped.
StValMult
: The set operate current can be changed by activation of the binary input
ENMULT to the set factor
StValMult
.
7.4
Directional residual overcurrent protection, four
steps EF4PTOC
IP14509-1 v8
7.4.1
Identification
M14881-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent
protection, four steps
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
51N_67N
7.4.2
Application
M12509-12 v10
The directional residual overcurrent protection, four steps EF4PTOC is used in
several applications in the power system. Some applications are:
Section 7
1MRK 504 169-UEN A
Current protection
120
Transformer protection RET650 2.2 IEC
Application manual
Содержание ret650
Страница 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Страница 2: ......
Страница 28: ...22...
Страница 38: ...32...
Страница 42: ...36...
Страница 80: ...74...
Страница 168: ...162...
Страница 174: ...168...
Страница 250: ...244...
Страница 346: ...340...
Страница 366: ...360...
Страница 390: ...384...
Страница 391: ...385...