10.9.1.1
Testing the liquid medium supervision for alarm and lock out conditions
1.
Connect binary inputs to consider gas pressure and gas density to initiate the
alarms.
2.
Consider the analogue pressure input
PRESSURE
to initiate the alarms.
3.
Gas pressure lock out input can be used to set
PRES_LO
signal, check the signal
status in local HMI under
Main menu/Test/Function status/Monitoring/Gas
medium supervision SSIMG/PRES_LO
4.
Reduce the pressure level input below
PresAlmLimit
, check for
PRES_ALM
signal status in local HMI under
Main menu/Test/Function status/
Monitoring/Gas medium supervision SSIMG/PRES_ALM
5.
Activate
BLOCK
binary input, the signals
PRES_ALM
,
PRES_LO
should
disappear.
6.
Reset the
BLOCK
binary input.
7.
Check for reset lock out input
RESET_LO
to reset
PRES_LO
lock out signal.
8.
Conduct these steps for temperature input as well to detect and reset
TEMP_ALM
and
TEMP_LO
signals.
9.
Continue to test another function or end the test by changing the
TESTMODE
setting to
off
.
10.9.1.2
Completing the test
Continue to test another function or end the test by changing the
TestMode
setting to
Off
. Restore connections and settings to their original values, if they were changed for
testing purposes.
10.9.2
Liquid medium supervision SSIML
Prepare the IED for verification of settings as outlined in section
in this chapter.
Check that the input logical signal
BLOCK
is logical zero and that on the local HMI,
the logical signals
LVL_ALM
,
LVL_LO
,
TEMP_ALM
and
TEMP_LO
are equal to
logical zero.
10.9.2.1
Testing the liquid medium supervision for alarm and lock out conditions
1.
Connect the binary inputs to consider liquid level to initiate the alarms.
2.
Consider the analogue level input
LEVEL
to initiate the alarms.
3.
Liquid level lock out input can be used to set
LVL_LO
signal, check the signal
status in local HMI under
Main menu/Test/Function status/Monitoring/
Liquid medium supervision SSIML/LVL_LO
4.
Reduce the liquid level input below LevelAlmLimit, check for
LVL_ALM
signal
status in local HMI under
Main menu/Test/Function status/Monitoring/
Liquid medium supervision SSIML/LVL_ALM
1MRK 504 160-UEN -
Section 10
Testing functionality by secondary injection
Transformer protection RET650 2.1 IEC
93
Commissioning manual
Содержание RET650 2.1 IEC
Страница 1: ...Relion 650 series Transformer protection RET650 2 1 IEC Commissioning manual ...
Страница 2: ......
Страница 24: ...18 ...
Страница 32: ...26 ...
Страница 48: ...42 ...
Страница 52: ...46 ...
Страница 72: ...66 ...
Страница 110: ...104 ...
Страница 116: ...110 ...
Страница 125: ...119 ...