BitA
RegA
IEC 61850 name
SA name
Description
Values
3231
201.15
.mcd
.mom-only
Mom only alternative
3232
202.00
.SPCSO1.stVal
X110-Output 1 State
0/1=Off/On
3233
202.01
.mcd
.mom-only
Mom only alternative
3234
202.02
.SPCSO2.stVal
X110-Output 2 State
0/1=Off/On
3235
202.03
.mcd
.mom-only
Mom only alternative
3236
202.04
.SPCSO3.stVal
X110-Output 3 State
0/1=Off/On
3237
202.05
.mcd
.mom-only
Mom only alternative
3238
202.06
.SPCSO4.stVal
X110-Output 4 State
0/1=Off/On
3239
202.07
.mcd
.mom-only
Mom only alternative
2.3.1.72
LD0.XGGIO130 Physical I/O states (BIO card X130)
Table 75:
LD0.XGGIO130 Physical I/O states (BIO card X130)
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.XGGIO130
3184
199.00
.Ind1.stVal
X130-Input 1 State
0/1=Off/On
3185
199.01
.mcd
.mom-only
Mom only alternative
3186
199.02
.Ind2.stVal
X130-Input 2 State
0/1=Off/On
3187
199.03
.mcd
.mom-only
Mom only alternative
3188
199.04
.Ind3.stVal
X130-Input 3 State
0/1=Off/On
3189
199.05
.mcd
.mom-only
Mom only alternative
3190
199.06
.Ind4.stVal
X130-Input 4 State
0/1=Off/On
3191
199.07
.mcd
.mom-only
Mom only alternative
3192
199.08
.Ind5.stVal
X130-Input 5 State
0/1=Off/On
3193
199.09
.mcd
.mom-only
Mom only alternative
3194
199.10
.Ind6.stVal
X130-Input 6 State
0/1=Off/On
3195
199.11
.mcd
.mom-only
Mom only alternative
3264
204.00
.SPCSO1.stVal
X130-Output 1 State
0/1=Off/On
Table continues on next page
1MRS756878 H
Section 2
Modbus data mappings
RET615
45