![ABB RET615 Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/abb/ret615/ret615_manual_2840023.webp)
Function
IEC 61850
A
B
C
D
E
F
G
H
TE01
TE02
TE03
TE04
TE05
TE06
TE07
TE08
Analog value scaling (4 pcs)
SCA4GAPC
4
4
4
4
4
4
4
4
Integer value move (4 pcs)
MVI4GAPC
1
1
1
1
1
1
1
1
1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in the
standard configuration.
() = optional
HV = The function block is to be used on the high-voltage side in the application.
LV = The function block is to be used on the low-voltage side in the application.
1) "Io calculated" is always used.
2) IoB calculated is always used.
3) "IoB measured" is always used.
4) Master trip is included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If additionally
the ARC option is selected, ARCSARC is connected in the configuration to the corresponding master trip input.
5) "IoB calculated" and "3IB" are always used.
6) Available only with IEC 61850-9-2
7) Available only with COM0031-0037
2.3
Indications
Table 3:
Explanations of the indications table columns
Column name
Description
BitA
Default 0X and 1X bit address for the data.
RegA
Default 3X and 4X register.bit (00-15) address for the data.
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as Logical
Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the
same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the value states.
2.3.1
Premapped indications
2.3.1.1
Common data 1
Table 4:
Common data 1
BitA
RegA
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
2720
170.00
.Loc.stVal
-
Remote/Local state
0/1=Rem/Loc
2721
170.01
.LocKeyHMI.stVal.Statio
n
-
Station state
1=Station
DR.RDRE1
2722
170.02
.RcdMade.stVal
-
DR recording made
1=Made
2723
170.03
.mcd
1MRS756878 H
Section 2
Modbus data mappings
RET615
17
Point List Manual