set the PMU Connection Tester parameters in order to establish an IEEE C37.118
connection with the PMU.
9.5.1
Verifying the IEEE C37.118/1344 TCP communication
After setting both PMU configuration and the TCP client configuration (As explained in
sections
Setting the PMU station communication (PMU Report)
communication (PMU configuration)
Setting the TCP/UDP client communication
and making sure that the Ethernet communication is set up, click
Connect
on the PMU
Connection Tester tool.
IEC140000138-1-en.vsd
IEC140000138 V1 EN
Figure 11:
Verifying the TCP communication using PMU Connection Tester
•
Now it should be possible to see the streaming synchrophasor data. In the
Graph
tab,
observe the Frequency, data Reporting Rate, Phasor names, and Phase angles of the
reported synchrophasors. Observe the real-time frame details of the Data Frame in the
bottom of the window.
1MRK 511 366-UUS -
Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
71
Commissioning manual