Section 4
1MAC309294-MB F
Protection functions
204
RER620
Technical Manual
27 prevents sensitive equipment from running under conditions that could cause
overheating and thus shorten their life time expectancy. In many cases, 27 is a useful
function in circuits for local or remote automation processes in the power system.
4.3.2.7
Signals
Table 211: 27-1/2 Input signals
Table 212: 27-1/2 Output signals
4.3.2.8
Settings
Table 213: 27-1/2 Group settings
Name
Type
Default
Description
V_A_AB
SIGNAL
0
Phase to ground voltage A or phase to phase voltage AB
V_B_BC
SIGNAL
0
Phase to ground voltage B or phase to phase voltage BC
V_C_CA
SIGNAL
0
Phase to ground voltage C or phase to phase voltage CA
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Name
Type
Description
OPERATE
BOOLEAN
Trip
OPR_A_AB
BOOLEAN
Trip output of Phase A (or Phase AB)
OPR_B_BC
BOOLEAN
Trip output of Phase B (or Phase BC)
OPR_C_CA
BOOLEAN
Trip output of Phase C (or Phase CA)
START
BOOLEAN
Pickup
ST_A_AB
BOOLEAN
Pickup output of Phase A (or Phase AB)
ST_B_BC
BOOLEAN
Pickup output of Phase B (or Phase BC)
ST_C_CA
BOOLEAN
Pickup output of Phase C (or Phase CA)
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.05...1.20
xVn
0.01
0.90
Pickup value
Time multiplier
0.05...15.00
0.05
1.00
Time multiplier in IEC/ANSI IDMT curves
Trip delay time
60...300000
ms
10
60
Trip delay time
Operating curve type
5=ANSI DT
15=IEC DT
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
5=ANSI DT
Selection of time delay curve type
Type of reset curve
1=Immediate
2=Def time reset
-1=DT Lin decr rst
1=Immediate
Selection of reset curve type
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......