1MAC309294-MB F
Section 4
Protection functions
RER620
203
Technical Manual
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting
Configuration > System > Blocking
mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the relay program. The
influence of the
BLOCK
input signal activation is preselected with the global
Blocking
mode
setting.
The
Blocking mode
setting has three blocking methods. In the “Freeze timers” mode, the
operate timer is frozen to the prevailing value. In the “Block all” mode, the whole function
is blocked and the timers are reset. In the “Block TRIP output” mode, the function operates
normally but the
TRIP
output is not activated.
4.3.2.5
Timer characteristics
The operating curve types supported by 27 are:
Table 210: Supported IDMT operate curve types
4.3.2.6
Application
27 is applied to power system elements, such as generators, transformers, motors and
power lines, to detect low voltage conditions. Low voltage conditions are caused by
abnormal operation or a fault in the power system. 27 can be used in combination with
overcurrent protections. Other applications are the detection of a no-voltage condition, for
example before the energization of a high voltage line, or an automatic breaker trip in case
of a blackout. 27 is also used to initiate voltage correction measures, such as insertion of
shunt capacitor banks, to compensate for a reactive load and thereby to increase the
voltage.
27 can be used to disconnect from the network devices, such as electric motors, which are
damaged when subjected to service under low voltage conditions. 27 deals with low
voltage conditions at power system frequency. Low voltage conditions can be caused by:
• Malfunctioning of a voltage regulator or incorrect settings under manual control
(symmetrical voltage decrease)
• Overload (symmetrical voltage decrease)
• Short circuits, often as phase-to-ground faults (unsymmetrical voltage increase).
The “Freeze timers” mode of blocking has no effect during the “Inverse
reset” mode.
Operating curve type
(5) ANSI Def. Time
(15) IEC Def. Time
(21) Inv. Curve A
(22) Inv. Curve B
(23) Programmable
Содержание RER620
Страница 1: ...Relion Protection and Control Advanced Recloser Protection and Control RER620 Technical Manual ...
Страница 2: ......
Страница 22: ...Section 1MAC309294 MB F 16 RER620 Technical Manual ...
Страница 88: ...Section 3 1MAC309294 MB F Basic functions 82 RER620 Technical Manual ...
Страница 278: ...Section 4 1MAC309294 MB F Protection functions 272 RER620 Technical Manual ...
Страница 362: ...Section 5 1MAC309294 MB F Control functions 356 RER620 Technical Manual ...
Страница 418: ...Section 7 1MAC309294 MB F Measurement functions 412 RER620 Technical Manual ...
Страница 428: ...Section 8 1MAC309294 MB F Recording functions 422 RER620 Technical Manual ...
Страница 464: ...Section 9 1MAC309294 MB F Other functions 458 RER620 Technical Manual ...
Страница 554: ...Section 10 1MAC309294 MB F General function block features 548 RER620 Technical Manual ...
Страница 568: ...Section 12 1MAC309294 MB F Relay physical connections 562 RER620 Technical Manual ...
Страница 574: ...Section 13 1MAC309294 MB F Technical data 568 RER620 Technical Manual ...
Страница 576: ...Section 14 1MAC309294 MB F Relay and functionality tests 570 RER620 Technical Manual ...
Страница 578: ...Section 15 1MAC309294 MB F Applicable standards and regulations 572 RER620 Technical Manual ...
Страница 582: ...Section 16 1MAC309294 MB F Glossary 576 RER620 Technical Manual ...
Страница 583: ......