Monitoring of AC analog measurements
&KDSWHU
0RQLWRULQJ
'HVLJQ
The design of the alternating quantities measuring function follows the design of all
REx 5xx-series protection, control, and monitoring terminals that have distributed func-
tionality, where the decision levels are placed as closely as possible to the process.
The measuring function uses the same input current and voltage signals as other protec-
tion and monitoring functions within the terminals. The number of input current and
voltage transformers depends on the type of terminal and options included. The maxi-
mum possible configuration comprises five current and five voltage input channels.
Measured input currents and voltages are first filtered in analog filters and then convert-
ed to numerical information by an A/D converter, which operates with a sampling fre-
quency of 2 kHz.
The numerical information on measured currents and voltages continues over a serial
link to one of the built-in digital signal processors (DSP). An additional Fourier filter
numerically filters the received information, and the DSP calculates the corresponding
values for the following quantities:
•
Five input measured voltages (U1, U2, U3, U4, U5), RMS values
•
Five input measured currents (I1, I2, I3, I4, I5), RMS Values
•
Mean RMS phase value, U, calculated from the first two phase-to-earth voltages U1
and U2 (two phase system) or the voltage from U1 (single phase system)
•
Mean RMS value, I, of the first two measured RMS values I1 and I2 (two phase sys-
tem) or the first measured RMS value I1 (single phase system)
•
Total active power, P, related to the first two measured currents and voltages (I1,
U1, I2, U2, two phase system) or related to I1 and U1 (single phase system)
•
Total reactive power, Q, related to the first two measured currents and voltages (I1,
U1, I2, U2, two phase system) or related to I1 and U1 (single phase system)
•
Total apparent power, S, related to the first two measured currents and voltages (I1,
U1, I2, U2, two phase system) or related to I1 and U1 (single phase system)
•
Mean value of frequencies, f, as measured with voltages U1 and U2 or just U1
Содержание REO 517
Страница 10: ... RQWHQWV ...
Страница 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Страница 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Страница 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Страница 100: ...90 Time delayed phase and residual overcurrent protection TOC1 KDSWHU XUUHQW Equation 36 Iset IsSEC I1b 100 ...
Страница 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Страница 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Страница 171: ...161 About this chapter KDSWHU RQWURO KDSWHU RQWURO ERXW WKLV FKDSWHU This chapter describes the control functions ...
Страница 293: ...283 About this chapter KDSWHU RJLF KDSWHU RJLF ERXW WKLV FKDSWHU This chapter describes the logic functions ...
Страница 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Страница 379: ...369 About this chapter KDSWHU 0HWHULQJ KDSWHU 0HWHULQJ ERXW WKLV FKDSWHU This chapter describes the metering functions ...
Страница 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Страница 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Страница 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...