![ABB REM615 ANSI Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/abb/rem615-ansi/rem615-ansi_manual_2834039.webp)
2.3.3.3
LD0.CSMSQI1 Sequence of currents
Table 77:
LD0.CSMSQI1 Sequence of currents
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.CSMSQI1
Sequence of currents
.SeqA.c1.instCVal.mag
I1_INST
-Positive magnitude
0.00..40.0 [xIn]
R
0,40,0,4000
.SeqA.c2.instCVal.mag
I2_INST
-Negative magnitude
0.00..40.0 [xIn]
R
0,40,0,4000
.SeqA.c3.instCVal.mag
I3_INST
-Zero magnitude
0.00..40.0 [xIn]
R
0,40,0,4000
2.3.3.4
CTRL.DCSXSWI1 Disconnector 1, 4-pole (2 bit) position values
Table 78:
CTRL.DCSXSWI1 Disconnector 1, 4-pole (2 bit) position values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCSXSWI1
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.3.3.5
CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values
Table 79:
CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCSXSWI2
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.3.3.6
CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values
Table 80:
CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCSXSWI3
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.3.3.7
CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2 bit) position
values
Table 81:
CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2 bit) position values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCXSWI1
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
1MRS756880 C
Section 2
DNP3 data mappings
REM615
33
Point List Manual