![ABB REM615 ANSI Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/abb/rem615-ansi/rem615-ansi_manual_2834034.webp)
2.3.2
Binary outputs
Table 60:
Explanations of the binary output table columns
Column name
Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible for example in ACT.
Description
Short description of the signal. See the application function block documentation
for more details.
Type
Output type. Some outputs can only be controlled with value “On”. Writing “Off” to
these points does not affect the function of the output. See DNP3 control relay
output block parameters.
2.3.2.1
CTRL.CBCSWI1 Circuit breaker control
Table 61:
CTRL.CBCSWI1 Circuit breaker control
IEC 61850 name
SA name
Description
Type
CTRL.CBCSWI1
.Pos.Oper.ctlVal
-
Circuit breaker control
On/Off
2.3.2.2
CTRL.DCCSWI1 Controllable disconnector (1) control
Table 62:
CTRL.DCCSWI1 Controllable disconnector (1) control
IEC 61850 name
SA name
Description
Type
CTRL.DCCSWI1
.Pos.Oper.ctlVal
-
Disconnector control
On/Off
2.3.2.3
CTRL.DCCSWI2 Controllable disconnector (2) control
Table 63:
CTRL.DCCSWI2 Controllable disconnector (2) control
IEC 61850 name
SA name
Description
Type
CTRL.DCCSWI2
.Pos.Oper.ctlVal
-
Disconnector control
On/Off
2.3.2.4
CTRL.ESCSWI2 Controllable earth switch (1) control
Table 64:
CTRL.ESCSWI2 Controllable earth switch (1) control
IEC 61850 name
SA name
Description
Type
CTRL.ESCSWI1
.Pos.Oper.ctlVal
-
Earth switch control
On/Off
Section 2
1MRS756880 C
DNP3 data mappings
28
REM615
Point List Manual