![ABB REM615 ANSI Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/abb/rem615-ansi/rem615-ansi_manual_2834032.webp)
2.3.1.50
LD0.TRPPTRC2 Global conditioning (2)
Table 53:
LD0.TRPPTRC2 Global conditioning (2)
IEC 61850 name
SA name
Description
Values
.Op.general
-
Operate input signal
1=Operate
.Tr.general
-
Trip output signal
1=Trip
2.3.1.51
LD0.VMMXU1 Three-phase voltage limit supervision
Table 54:
LD0.VMMXU1 Three-phase voltage limit supervision
IEC 61850 name
SA name
Description
Values
LD0.VMMXU1
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
.LoAlm.stVal
LOW_ALARM
Low alarm
1=Alarm
.LoWrn.stVal
LOW_WARN
Low warning
1=Warning
2.3.1.52
LD0.XRGGIO130 Alarm/warning
Table 55:
LD0.XRGGIO130 Alarm/warning
IEC 61850 name
SA name
Description
Values
LD0.XRGGIO130
.Alm.stVal
-
XRGGIO130 Alarm
1=Alarm
.Wrn.stVal
-
XRGGIO130 Warning
1=Warning
2.3.1.53
LD0.XAGGIO130 Physical I/O
Table 56:
LD0.XAGGIO130 Physical I/O
IEC 61850 name
SA name
Description
Values
LD0.XAGGIO130
.Ind1.stVal
-
X130-Input 1
1/0=ON/OFF
.Ind2.stVal
-
X130-Input 2
1/0=ON/OFF
.Ind3.stVal
-
X130-Input 3
1/0=ON/OFF
.Ind4.stVal
-
X130-Input 4
1/0=ON/OFF
Section 2
1MRS756880 C
DNP3 data mappings
26
REM615
Point List Manual