19.9
Ingress protection
Table 566:
Ingress protection
Description
Value
IED front
IP 54
IED rear
IP 20
IED sides
IP 40
IED top
IP 40
IED bottom
IP 20
19.10
Environmental conditions and tests
Table 567:
Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC (continuous)
Short-time service temperature range
-40...+70ºC (<16h)
Note: Degradation in MTBF and HMI performance
outside the temperature range of -25...+55ºC
Relative humidity
<93%, non-condensing
Atmospheric pressure
12.47...15.37 psi (86...106 kPa)
Altitude
up to 6561.66 feet (2000 m)
Transport and storage temperature range
-40...+85ºC
Table 568:
Environmental tests
Description
Type test value
Reference
Cold tests
operation
storage
96 h at -25ºC
16 h at -40ºC
96 h at -40ºC
IEC 60068-2-1/ANSI
C37.90-2005 (chapter 4)
Dry heat tests
operation
storage
16 h at +70ºC
96 h at +85ºC
IEC 60068-2-2/ANSI
C37.90-2005 (chapter 4)
Damp heat tests
steady state
cyclic
240 h at +40ºC
humidity 93%
6 cycles at +25 to +55ºC
humidity 93...95%
IEC 60068-2-78
IEC 60068-2-30
Section 19
1MRK 502 048-UUS A
Technical data
728
Technical manual