Table 242:
A1A2_DC (3) Output signals
Name
Type
Description
089OPREL
BOOLEAN
Opening of 089 is allowed
089OPITL
BOOLEAN
Opening of 089 is not allowed
089CLREL
BOOLEAN
Closing of 089 is allowed
089CLITL
BOOLEAN
Closing of 089 is not allowed
DCOPTR
BOOLEAN
The bus section disconnector is in open position
DCCLTR
BOOLEAN
The bus section disconnector is in closed position
VPDCTR
BOOLEAN
Switch status of 089 is valid (open or closed)
12.3.5.6
Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
12.3.6
Interlocking for bus-coupler bay ABC_BC (3)
12.3.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-coupler bay
ABC_BC
-
3
12.3.6.2
Functionality
The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler bay
connected to a double busbar arrangement according to figure
. The function can also
be used for a single busbar arrangement with transfer busbar or double busbar
arrangement without transfer busbar.
Section 12
1MRK 502 048-UUS A
Control
392
Technical manual