Table 35:
Limits for the RTD/mA inputs
Input mode
Description
Not in use
Default selection. Used when the corresponding input is not used.
0...20 mA
Selection for analog DC milliampere current inputs in the input range of 0...20 mA.
Resistance
Selection for RTD inputs in the input range of 0...2000 Ω.
Pt100
Pt250
Ni100
Ni120
Ni250
Cu10
Selection for RTD inputs, when temperature sensor is used. All the selectable
sensor types have their resistance vs. temperature characteristics stored in the
module; default measuring range is -40...200°C.
3.12.2.2
Selection of output value format
Each input has independent
Value unit
settings that are used to select the unit for the
channel output. The default value for the
Value unit
setting is “Dimensionless”.
Input
minimum
and
Input maximum
, and
Value maximum
and
Value minimum
settings have
to be adjusted according to the input channel. The default values for these settings are
set to their maximum and minimum setting values.
When the channel is used for temperature sensor type, set the
Value unit
setting to
“Degrees celsius”. When
Value unit
is set to “Degrees celsius”, the linear scaling is not
possible, but the default range (-40…200 °C) can be set smaller with the
Value
maximum
and
Value minimum
settings.
When the channel is used for DC milliampere signal and the application requires a
linear scaling of the input range, the
Value unit
setting value has to be
"Dimensionless”, where the input range can be linearly scaled with settings
Input
minimum
and
Input maximum
to
Value minimum
and
Value maximum
. When
milliampere is used as an output unit,
Value unit
has to be "Ampere”. When
Value unit
is set to “Ampere”, the linear scaling is not possible, but the default range (0…20 mA)
can be set smaller with the
Value maximum
and
Value minimum
settings.
When the channel is used for resistance type signals and the application requires a
linear scaling of the input range, the
Value unit
setting value has to be
"Dimensionless”, where the input range can be linearly scaled with the setting
Input
minimum
and
Input maximum
to
Value minimum
and
Value maximum
. When
resistance is used as an output unit,
Value unit
has to be "Ohm". When
Value unit
is
set to “Ohm”, the linear scaling is not possible, but the default range (0…2000 Ω) can
be set smaller with the
Value maximum
and
Value minimum
settings.
3.12.2.3
Input linear scaling
Each RTD/mA input can be scaled linearly by the construction of a linear output
function in respect to the input. The curve consists of two points, where the y-axis
(
Input minimum
and
Input maximum
) defines the input range and the x-axis (
Value
minimum
and
Value maximum
) is the range of the scaled value of the input.
Section 3
1MRS758755 A
Basic functions
88
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...