t s
k A
B
U
U
U
C
D
E
=
⋅
×
< −
<
−
+
GUID-4A433D56-D7FB-412E-B1AB-7FD43051EE79 V2 EN
(Equation 86)
t[s] operate time in seconds
A
the set value of
Curve parameter A
B
the set value of
Curve parameter B
C
the set value of
Curve parameter C
D
the set value of
Curve parameter D
E
the set value of
Curve parameter E
U
measured voltage
U< the set value of
Start value
k
the set value of
Time multiplier
11.3.2.3
IDMT curve saturation of undervoltage protection
For the undervoltage IDMT mode of operation, the integration of the operate time
does not start until the voltage falls below the value of
Start value
. To cope with
discontinuity characteristics of the curve, a specific parameter for saturating the
equation to a fixed value is created. The
Curve Sat Relative
setting is the parameter and
it is given in percents compared with
Start value
. For example, due to the curve
equation B, the characteristics equation output is saturated in such a way that when
input voltages are in the range from
Start value
to
Curve Sat Relative
in percents under
Start value
, the equation uses
Start value
* (1.0 -
Curve Sat Relative
/ 100 ) for the
measured voltage. Although, the curve A has no discontinuities when the ratio U/U>
exceeds the unity,
Curve Sat Relative
is set for it as well. The
Curve Sat Relative
setting for curves A, B and C is 2.0 percent. However, it should be noted that the user
must carefully calculate the curve characteristics concerning also discontinuities in
the curve when the programmable curve equation is used. Thus, the
Curve Sat Relative
parameter gives another degree of freedom to move the inverse curve on the voltage
ratio axis and it effectively sets the maximum operate time for the IDMT curve
because for the voltage ratio values affecting by this setting, the operation time is
fixed, that is, the definite time, depending on the parameters but no longer the voltage.
11.4
Frequency measurement and protection
All the function blocks that use frequency quantity as their input signal share the
common features related to the frequency measurement algorithm. The frequency
estimation is done from one phase (phase-to-phase or phase voltage) or from the
positive phase sequence (PPS). The voltage groups with three-phase inputs use PPS as
the source. The frequency measurement range is 0.6...1.5 × F
n
. The df/dt measurement
range always starts from 0.6 × F
n
. When the frequency exceeds these limits, it is
Section 11
1MRS758755 A
General function block features
756
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...