![ABB RELION Series Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191070.webp)
Behavior data objects under CTRL logical device follow
CTRL.LLN0.Mod value. If "On" is selected, behavior data objects
follow the mode of the corresponding logical device.
3.6.5
Application configuration and Control mode
The physical outputs from commands to process are blocked with “Blocked“ mode. If
physical outputs need to be blocked totally, meaning also commands from the binary
inputs, the application configuration must be used to block these signals. Blocking
scheme uses
BEH_BLK
output of CONTROL function block.
3.6.6
Authorization
By default,
Test mode
and
Control mode
can only be changed from LHMI. It is
possible to write test mode by remote client, if it is needed in configuration. This is
done via LHMI only by setting the
Remote test mode
parameter via
Tests/IED test/
Test mode
. Remote operation is possible only when control position of the relay is in
remote position. Local and remote control can be selected with R/L button or via
Control function block in application configuration.
When using the Signal Monitoring tool to force online values, the following
conditions need to be met.
•
Remote force
is set to “All levels”
•
Test mode
is enabled
•
Control position of the relay is in remote position
Table 21:
Remote test mode
Remote test mode
61850-8-1-MMS
WHMI/PCM600
Off
No access
No access
Maintenance
Command originator category maintenance No access
All levels
All originator categories
Yes
3.6.7
LHMI indications
The yellow Start LED flashes when the relay is in “IED blocked” or “IED test and
blocked” mode. The green Ready LED flashes to indicate that the “IED test and
blocked” mode or "IED test" mode is activated.
Section 3
1MRS758755 A
Basic functions
64
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...