Table 19:
Test mode
Test mode
Description
Protection BEH_BLK
Normal mode
Normal operation
FALSE
IED blocked
Protection working as in “Normal mode” but ACT
configuration can be used to block physical
outputs to process. Control function commands
blocked.
TRUE
IED test
Protection working as in “Normal mode” but
protection functions are working in parallel with
test parameters.
FALSE
IED test and blocked
Protection working as in “Normal mode” but
protection functions are working in parallel with
test parameters. ACT configuration can be used to
block physical outputs to process. Control function
commands blocked.
TRUE
Behavior data objects in all logical nodes follow LD0.LLN0.Mod
value. If "Normal mode" is selected, behaviour data objects follow
mode (.Mod) data object of the corresponding logical device.
Vertical and horizontal communication is not blocked by the “IED
blocked” or “IED test and blocked” modes.
3.6.3
Application configuration and Test mode
The physical outputs from control commands to process are blocked with ”IED
blocked” and “IED test and blocked” modes. If physical outputs need to be blocked
from the protection, the application configuration must be used to block these signals.
Blocking scheme needs to use
BEH_BLK
output of PROTECTION function block.
3.6.4
Control mode
The mode of all logical nodes located under CTRL logical device can be set with
Control mode
. The
Control mode
parameter is available via the HMI or PCM600 path
Configuration/Control/General
. By default,
Control mode
can only be set locally
through LHMI.
Control mode
inherits its value from
Test mode
but
Control
mode
”On”, “Blocked” and “Off” can also be set independently.
Control mode
is also
available via IEC 61850 communication (CTRL.LLN0.Mod).
Table 20:
Control mode
Control mode
Description
Control BEH_BLK
On
Normal operation
FALSE
Blocked
Control function commands blocked
TRUE
Off
Control functions disabled
FALSE
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
63
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...