Parameter
Values (Range)
Unit
Step
Default
Description
Protection crd limit
1...5
1
1
Protection coordination shot limit
Protection crd mode
1=No condition
2=AR inoperative
3=CB close manual
4=AR inop, CB man
5=Always
4=AR inop, CB
man
Protection coordination mode
Control line
0...63
1
63
Control line, defines INIT inputs which are
protection signals
Enable shot jump
0=False
1=True
1=True
Enable shot jumping
CB closed Pos status
0=False
1=True
0=False
Circuit breaker closed position status
Blk signals CBB1
0...63
1
0
Blocking lines for CBB1
Blk signals CBB2
0...63
1
0
Blocking lines for CBB2
Blk signals CBB3
0...63
1
0
Blocking lines for CBB3
Blk signals CBB4
0...63
1
0
Blocking lines for CBB4
Blk signals CBB5
0...63
1
0
Blocking lines for CBB5
Blk signals CBB6
0...63
1
0
Blocking lines for CBB6
Blk signals CBB7
0...63
1
0
Blocking lines for CBB7
Str 2 delay shot 1
0...300000
ms
10
0
Delay time for start2, 1st reclose
Str 2 delay shot 2
0...300000
ms
10
0
Delay time for start2 2nd reclose
Str 2 delay shot 3
0...300000
ms
10
0
Delay time for start2 3rd reclose
Str 2 delay shot 4
0...300000
ms
10
0
Delay time for start2, 4th reclose
Str 3 delay shot 1
0...300000
ms
10
0
Delay time for start3, 1st reclose
Str 3 delay shot 2
0...300000
ms
10
0
Delay time for start3 2nd reclose
Str 3 delay shot 3
0...300000
ms
10
0
Delay time for start3 3rd reclose
Str 3 delay shot 4
0...300000
ms
10
0
Delay time for start3, 4th reclose
Str 4 delay shot 1
0...300000
ms
10
0
Delay time for start4, 1st reclose
Str 4 delay shot 2
0...300000
ms
10
0
Delay time for start4 2nd reclose
Str 4 delay shot 3
0...300000
ms
10
0
Delay time for start4 3rd reclose
Str 4 delay shot 4
0...300000
ms
10
0
Delay time for start4, 4th reclose
9.4.9
Monitored data
Table 671:
DARREC Monitored data
Name
Type
Values (Range)
Unit
Description
DISA_COUNT
BOOLEAN
0=False
1=True
Signal for counter
disabling
FRQ_OPR_CNT
INT32
0...2147483647
Frequent operation
counter
FRQ_OPR_AL
BOOLEAN
0=False
1=True
Frequent operation
counter alarm
Table continues on next page
1MRS758755 A
Section 9
Control functions
REC615 and RER615
663
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...