9.2.9
Technical revision history
Table 652:
DCSXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s and
30 s respectively for
Event delay settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced to
“FALSE” in case status is Faulty (11).
Table 653:
ESSXSWI Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s and
30 s respectively for
Event delay settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced to
“FALSE” in case status is Faulty (11).
9.3
Synchronism and energizing check SECRSYN
9.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Synchronism and energizing check
SECRSYN
SYNC
25
9.3.2
Function block
GUID-9270E059-ED17-4355-90F0-3345E1743464 V2 EN
Figure 314:
Function block
9.3.3
Functionality
The synchronism and energizing check function SECRSYN checks the condition
across the circuit breaker from separate power system parts and gives the permission
to close the circuit breaker. SECRSYN includes the functionality of synchrocheck and
energizing check.
1MRS758755 A
Section 9
Control functions
REC615 and RER615
617
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...