![ABB RELION Series Скачать руководство пользователя страница 615](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191615.webp)
Local/Remote operations
The local/remote selection affects CBXCBR and DCXSWI.
•
Local: the opening and closing via communication is disabled.
•
Remote: the opening and closing via LHMI is disabled.
•
AU_OPEN
and
AU_CLOSE
inputs function regardless of the local/remote
selection.
9.1.5
Application
In the field of distribution and sub-transmission automation, reliable control and
status indication of primary switching components both locally and remotely is in a
significant role. They are needed especially in modern remotely controlled
substations.
Control and status indication facilities are implemented in the same package with
CBXCBR and DCXSWI. When primary components are controlled in the energizing
phase, for example, the correct execution sequence of the control commands must be
ensured. This can be achieved, for example, with interlocking based on the status
indication of the related primary components. The interlocking on substation level can
be applied using the IEC 61850 GOOSE messages between feeders.
Control and interlocking via GOOSE messages
REF 615
REF 615
REF 615
REF 615
A070879 V3 EN
Figure 311:
Status indication-based interlocking via the GOOSE messaging
1MRS758755 A
Section 9
Control functions
REC615 and RER615
609
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...