Figure 252:
Fault loop impedance for phase-to-phase fault loops (either “AB
Fault”, “BC Fault” or “CA Fault”)
The fault distance calculation algorithm for the phase-to-phase fault loops is defined
by using settings
Load Com PP loops
and
Enable simple model
. Options for the
selection are "Disabled" or "Enabled".
Load compensation can be enabled or disabled with setting
Load Com PP loops
. The
load compensation should be disabled only if the ratio between the fault current and
load current is large or when the value of the fault distance estimate for the short circuit
fault is required from each shot of an autoreclosing sequence.
The fault distance calculation is most accurate when calculated with the fault loop
model. This model requires positive sequence impedances of the protected feeder to
be given as settings. If these settings are not available, valid impedance values can be
calculated also without the fault loop model with setting
Enable simple model
=
“TRUE”. However, valid distance estimate, that is, the conversion of measured
impedance (‘’electrical fault distance’’) into a physical fault distance requires
accurate positive sequence impedance settings.
Fault loop “ABC Fault”
Fault loop “ABC Fault” is used exclusively for the three-phase short circuit fault.
shows the three-phase fault loop model. The following impedances are
measured and stored in the recorded data of SCEFRFLO.
Flt point resistance
R
fault
=
GUID-2503378E-4AC5-4E9F-9D77-2E7C71592C37 V3 EN
(Equation 55)
Flt loop resistance
R
R
fault
=
+
1
GUID-F9E2B211-9C30-4A81-ABD4-525CC10AB7A8 V2 EN
(Equation 56)
Flt loop reactance
Flt phase reactance
X
=
=
1
GUID-049B892B-9031-4361-843B-7102E6A4DA17 V3 EN
(Equation 57)
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
489
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...