5.1.6
Signals
Table 491:
INRPHAR Input signals
Name
Type
Default
Description
I_2H_A
SIGNAL
0
Second harmonic phase A current
I_1H_A
SIGNAL
0
Fundamental frequency phase A current
I_2H_B
SIGNAL
0
Second harmonic phase B current
I_1H_B
SIGNAL
0
Fundamental frequency phase B current
I_2H_C
SIGNAL
0
Second harmonic phase C current
I_1H_C
SIGNAL
0
Fundamental frequency phase C current
BLOCK
BOOLEAN
0=False
Block input status
Table 492:
INRPHAR Output signals
Name
Type
Description
BLK2H
BOOLEAN
Second harmonic based block
5.1.7
Settings
Table 493:
INRPHAR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
5...100
%
1
20
Ratio of the 2. to the 1. harmonic leading
to restraint
Operate delay time
20...60000
ms
1
20
Operate delay time
Table 494:
INRPHAR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 495:
INRPHAR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
5.1.8
Monitored data
Table 496:
INRPHAR Monitored data
Name
Type
Values (Range)
Unit
Description
INRPHAR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Section 5
1MRS758755 A
Protection related functions
464
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...