![ABB RELION Series Скачать руководство пользователя страница 466](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191466.webp)
4.7.7
Settings
Table 486:
MAPGAPC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
-10000.0...10000.0
0.1
0.0
Start value
Start value Add
-100.0...100.0
0.1
0.0
Start value Add
Operate delay time
0...200000
ms
100
0
Operate delay time
Table 487:
MAPGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Over
2=Under
1=Over
Operation mode
Table 488:
MAPGAPC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
100
0
Reset delay time
Absolute hysteresis
0.01...100.00
0.01
0.10
Absolute hysteresis for operation
4.7.8
Monitored data
Table 489:
MAPGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
MAPGAPC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.7.9
Technical data
Table 490:
MAPGAPC Technical data
Characteristic
Value
Operation accuracy
±1.0% of the set value or ±20 ms
Section 4
1MRS758755 A
Protection functions
460
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...